Exit
JET Series

Inline centrifigal fan from 6" up to 10" inlet. Mounted on a roof curb or a inline, JET fans generate a high plume exhaust to ensure maximum dilution of gases in the environment. Smooth and quiet performance. Ideal for water treatment plants and fume hood exhaust applications.
Unit of Measure

Specifications

Wheel Diameter

N/A 11.81 in

Application

Application

N/A
The JET Series centrifugal inline fan is designed to work in highly corrosive air applications such as laboratory exhaust or the chemical industry. JET Series fans shall be installed on a roof curb or inline as specified.

Temperature Limitation

Temperature Limitation

N/A
Polypropylene casing and wheel recommended 140° F constant and up to 190° F for short periods of time.

Housing

Housing

N/A
Impellers/wheels shall be of forward-curved type and constructed of uniformly molded polypropylene blades. Impellers/Wheels shall be both electronically and dynamically balanced. Fan impeller/wheel shall be supplied with a motor shaft bushing and hubcap made of polypropylene to protect motor shaft end. Fan impeller/wheel shall be suitable for RPM of up to 3450 on models JET 20 and 25, and up to 1725 on model JET 30. Optional 304L stainless steel impeller/wheel available for models JET 20, JET 25 and JET 30.

Impeller/Wheel

Impeller/Wheel

N/A
Impellers/wheels shall be of forward-curved type and constructed of uniformly molded polypropylene blades. Impellers/Wheels shall be both electronically and dynamically balanced. Fan impeller/wheel shall be supplied with a motor shaft bushing and hubcap made of polypropylene to protect motor shaft end. Fan impeller/wheel shall be suitable for RPM of up to 3450 on models JET 20 and 25, and up to 1725 on model JET 30. Optional 304L stainless steel impeller/wheel available for models JET 20, JET 25 and JET 30.

Motors

Motors

N/A
Motors shall be direct drive and of heavy-duty, lubricated for life ball bearing type for continuous duty. Motors shall be totally enclosed fan cooled (TEFC), UL and CSA compliant. Motor shall be outside the air stream and pre-wired to a disconnect switch for safety. Some models available with explosion-proof motors. Consult with factory for availability.

Performance

Performance

N/A
Fan performance shall be based on tests conducted in accordance with AMCA 210-85 and ISO 5801.

Warranty

Warranty

N/A
Plastec Ventilation, Inc. warrants its equipment, products and parts, to be free from defects in workmanship and material under normal use and service for two years after delivery to the first user. Motors carry a one year warranty. (See full warranty on page 6 of the Installation, Operation & Maintenance Manual)